Sodium Hypochlorite Generating Equipment
DivisionDivision 46 Water and Wastewater Equipment
Section46 33 00 Liquid Chemical Feed Equipment
ApplicationsWater & Wastewater Infrastructure
PRODUCT

Sodium Hypochlorite Generating Equipment

Electrolytic generation · Dosing · Control — disinfection without bulk chlorine

Water Disinfection Electrochlorination On-site Generation
Overview

On-site sodium hypochlorite generation by electrolysis of brine, supplying disinfection for municipal and industrial potable water, wastewater effluent and tertiary treatment, and seawater or cooling water systems at ports and power plants. Generating on site removes bulk chlorine storage and transport from the site risk register.

Specification

The system generates sodium hypochlorite on demand from salt, water and electricity only: NaCl + H2O plus energy giving NaOCl + H2. A brine saturator produces 2.5-3.5 % w/w sodium chloride solution, passed through undivided electrolytic cells fitted with titanium mixed-metal-oxide anodes. Output is 2.7 kg/day to 500 kg/day per skid, expandable above 1000 kg/day by adding cell stacks, at a product strength of 0.8 % +/- 0.05 %. Consumption is 3.2-4.0 kg salt and 4.0-5.5 kWh DC per kg of chlorine produced, with current efficiency of 85-95 %.

Safe operation centres on hydrogen management. The cathodic by-product is diluted by a forced-draught fan to below 25 % of the lower explosive limit, equal to 1.0 vol % hydrogen in air, and discharged through a dedicated non-return vent stack, with float, flow and airflow interlocks plus a hydrogen detector. Control is by PLC with HMI touchscreen, 8-32 discrete I/O and 4-16 analogue channels, supporting SCADA, Modbus or Profinet telemetry. Skids include brine softening, acid-wash descaling, a 24-72 h hypochlorite day tank, and metering pumps for 0.5-5 mg/L residual dosing.

Standards
  • NSF/ANSI 61 — Health-effects requirements for drinking water system components; on-site hypochlorite generators are certified under this standard, with the generated effluent chemical identified in the listing footnote.
  • NSF/ANSI 60 — Health-effects standard for drinking water treatment chemicals, applied to the sodium chloride feedstock used in electrochlorination and to bromate, chlorate and perchlorate formation limits.
  • EN 901 — Chemicals used for treatment of water intended for human consumption - sodium hypochlorite; its impurity limits, purity criteria and pH range of 11-13 apply as quality benchmarks for the generated solution.
  • AWWA B300 — Standard for hypochlorites (sodium hypochlorite and calcium hypochlorite), including storage, temperature, dilution and pH control guidance that governs the handling of generated hypochlorite.
  • IEC 60079-10-1 / ATEX Directive 2014/34/EU — Classification of hazardous areas where hydrogen from the electrolysis cells may be released, and the selection of Zone 2 certified equipment, ventilation rates and flame arrestors.
  • NEMA 250 / IEC 60529 — Enclosure ratings for control panels and power supplies, typically IP54 to IP66 (NEMA 3R to 4X) for indoor plant rooms and outdoor desert installations.

Generated hypochlorite for potable duty is assessed to EN 901 and NSF/ANSI 60, with the salt supply to EN 12671. Local drinking water inspectorate acceptance is handled per project.

Applications
  • Municipal drinking water — treatment works and distribution network disinfection dosing.
  • Wellfields & storage — remote wellfields, booster stations and storage reservoir re-chlorination.
  • Wastewater & reuse — effluent disinfection for wastewater and reclaimed water discharge.
  • Desalination — product water conditioning and SWRO pretreatment chlorination.
  • Cooling & district cooling — cooling tower and district cooling circuits for Legionella and biofilm control.
  • Pools & leisure — swimming pools, water parks and leisure facility dosing.
  • Food & beverage — process water, CIP and bottle rinse disinfection.
  • Oil & gas — utility water and seawater injection systems on petrochemical sites.
  • Marine & offshore — marine growth control, ballast water treatment and offshore platforms.
Certificates & documentation
  • NSF/ANSI 61 certificate of compliance for the generator, with certified salt declaration under NSF/ANSI 60
  • ISO 9001, ISO 14001 and ISO 45001 management system certificates
  • Hazardous area classification and hydrogen ventilation dossier to IEC 60079-10-1 with ATEX / IECEx component certificates
  • Factory Acceptance Test report covering capacity, current efficiency, salt and energy consumption, and 72-hour continuous run
  • CE or UKCA declaration of conformity with EMC and low-voltage directive test reports
  • Anode coating warranty and performance guarantee (5-8 year anode life, output tonnage guarantee)
Supply capability
  • Design, manufacture, installation guidance and commissioning with operator training.
  • Spare parts and O&M support for the electrolyser and dosing system.
  • Export packing, FOB / CFR / CIF to Gulf ports.
Approval

Supplied to projects across the Gulf, North and Sub-Saharan Africa, South-East Asia and Australia. Middle East supplies are subject to project-specific approval by the owner, engineer or consultant; PROTEKTA prepares and supports the submittal package for that approval.

FREQUENT QUESTIONS

Sodium Hypochlorite Generating Equipment — Buyer Questions

How does the system work?

The unit electrolyses brine to generate sodium hypochlorite on site, with the control system interlocking pH, salinity, current and concentration. Dosing pumps and valves are supplied to the configured arrangement, removing bulk chlorine storage from the site. Supplied for projects across the GCC — Saudi Arabia, UAE, Qatar, Kuwait, Oman and Bahrain — and to Iraq, Algeria, Morocco, Nigeria, Ethiopia, Tanzania, Malaysia, Thailand, Singapore, Indonesia, Brunei and Australia, with compliance documentation prepared for consultant, contractor and authority submittal.

Where is it used?

Municipal and industrial potable water disinfection, wastewater effluent and tertiary treatment, seawater cooling water at ports and power plants, and desalination post-treatment. Also specified and procured as Sodium Hypochlorite Generator, Electrochlorination and On-site Chlorine Generation; full specification ranges, material grades and datasheets are issued for tender, submittal and procurement use.

Which standards and certifications apply?

Generated hypochlorite for potable duty is assessed to EN 901 and NSF/ANSI 60, with salt supply to EN 12671 and AWWA B300 where cited. Electrical and control equipment follows IEC 60204-1 and EN 61010. OEM, private-label and bespoke manufacture is supported for contractors, distributors and EPC packages.

Is commissioning and training included?

Yes. Design, manufacture, installation guidance, commissioning and operator training are provided, along with spare parts and O&M support. Export packing, third-party inspection and consolidated shipment to Gulf ports/global ports are arranged with the order.